  • Epoxy Resin Bushing Full Range: 1.2kV/1000~6500A High-Current, 24~36kV/250~630A and 35kV/315A — Three Series
Epoxy Resin Bushing Full Range: 1.2kV/1000~6500A High-Current, 24~36kV/250~630A and 35kV/315A — Three Series

Epoxy Resin Bushing Full Range: 1.2kV/1000~6500A High-Current, 24~36kV/250~630A and 35kV/315A — Three Series

Product Overview

This page summarizes Xingda's full range of epoxy resin bushings — three series, 27 specifications. The red epoxy-cast insulation is a dry, oil-free design; compared with porcelain, it is lighter and more explosion-proof, ideal for dry-type transformers, pad-mounted substations, switchgear and the LV compartments of European-style compact substations.

The three series: ① BFG series (1.2kV, 1000~6500A) LV high-current bushings — 18 specifications, terminal pads 80×80 to 125×125, cover openings Φ57~Φ150, each current step available with -90° / -0° terminal direction; ② 24~36kV series (250~630A) MV bushings — 4 specifications; ③ BFGW series (35kV, 315A) outdoor epoxy bushings — 5 configurations (external-thread stud W / internal-thread N; gland-plate flange P / cast-resin flange S), creepage 1256~1650 mm.

Designation: BFG-voltage/current-terminal angle (e.g. BFG-1/2000-90°); MV models are written as voltage/current (e.g. 36/630); outdoor types add W (BFGW-35KV/315A). Internal codes follow XD.GSTG.xx.A/B.

Models & Specifications

Table 1 | BFG series 1.2kV LV high-current bushings (1000~6500A, -90°/-0° terminal directions)

S/NModelHh2h3dd1d3d4B1×B2DbtB3×B4b3×b4t1σ1×σ2Opening d0Code
1BFG-1/1000-90°267111783055552680×8013301050×6022×261080×8057XD.GSTG.02.A
2BFG-1/1000-0°267111783055552680×8013301050×6022×261080×8057XD.GSTG.02.B
3BFG-1/1600-90°267111783670703180×8013451250×6022×261280×8072XD.GSTG.03.A
4BFG-1/1600-0°267111783670703180×8013451250×6022×261280×8072XD.GSTG.03.B
5BFG-1/2000-90°2871117842707031100×10013451250×6022×261580×8072XD.GSTG.04.A
6BFG-1/2000-0°2871117842707031100×10013451250×6022×261580×8072XD.GSTG.04.B
7BFG-1/3150-90°2871117848707031100×10013451650×6022×262080×8072XD.GSTG.05.A
8BFG-1/3150-0°2871117848707031100×10013451650×6022×262080×8072XD.GSTG.05.B
9BFG-1/4000-90°35414811552808031125×12518602075×8540×4520Φ13082XD.GSTG.06.A
10BFG-1/4000-0°35414811552808031125×12518602075×8540×4520Φ13082XD.GSTG.06.B
11BFG-1/5000-90°35414811556808031125×12518602075×8540×4520Φ13082XD.GSTG.07.A
12BFG-1/5000-0°35414811556808031125×12518602075×8540×4520Φ13082XD.GSTG.07.B
13BFG-1/5500-90°4451931406010010061125×12514602585×12345×5025Φ150102XD.GSTG.08.A
14BFG-1/5500-0°4451931406010010061125×12514602585×12345×5025Φ150102XD.GSTG.08.B
15BFG-1/6000-90°4451931406510010061125×12514602585×12345×5025Φ150102XD.GSTG.09.A
16BFG-1/6000-0°4451931406510010061125×12514602585×12345×5025Φ150102XD.GSTG.09.B
17BFG-1/6500-90°4451931407010010061125×12514603085×12345×5030Φ150102XD.GSTG.10.A
18BFG-1/6500-0°4451931407010010061125×12514603085×12345×5030Φ150102XD.GSTG.10.B

※ All dimensions in mm. Direction A mounting holes: 4-Φ20, 2-Φ8.5; direction B: 2-Φ14; tank fixing: 4-M10×50. d0 = 57/72/82 (round) for 1000~5000A; d0 = 102/Φ150 for 5500A and above.

Table 2 | 24~36kV MV bushings (250~630A)

ModelDd1d2d3d4d5Hh1h2h3h4d6d7Code
24/25011083132.573.5M10245345828116Φ80Φ123XD.GSTG.24-250
36/25011114455676M102384010227.593Φ80Φ140XD.GSTG.36-250
36/400128M16465688M163323410030157Φ90Φ140XD.GSTG.36-400
36/630128M16465688M163323410030157Φ90Φ140XD.GSTG.36-630

※ Cover fixing: 24/250 with 4-M10×55 (90° PCD); 36/250 with 4-M12×55 (120° PCD); 36/400 and 36/630 with 4-M10×60 (90° PCD). d1 = cable bore (8/14 mm for 250A; M16 stud for 400~630A).

Table 3 | BFGW-35kV outdoor epoxy bushings (315A, 5 configurations: external-thread stud W / internal-thread N; gland-plate flange P / cast-resin flange S)

ModelHh2h3Mdd1d2d3Opening d0Arcing h1CreepageCode
BFGW-35KV/315A58012240M12×1.754580901053651256XD.GSTG.02.A
BFGW-35KV/315A66012240M12×1.75145180901054451530XD.GSTG.02.B
BFGW-35KV/315A61014040M12×1.7542.52101001054001450XD.GSTG.03.A
BFGW-35KV/315A64013040M12×1.751462401001054071450XD.GSTG.03.B
BFGW-35KV/315A75013040M12×1.751462401001055271650XD.GSTG.04.A

※ Two flange mountings: gland-plate flange (P, Φ250/Φ214, 6-M12 PCD) and cast-resin flange (S, Φ250/Φ184, 8-M12 PCD), fixing depth 8~10; studs available external-thread (W) or internal-thread (N). The mapping of code rows to W/N × P/S combinations is to be confirmed against drawings.

Typical Applications

ApplicationRecommended SeriesNotes
LV high-current outlet of dry-type transformers / compact substationsBFG-1/1000~6500Terminal pads up to 125×125, t1 up to 30, openings Φ57~Φ150
LV compartments of European-style substations, switchgearBFG-1/1000~3150-90°/-0° terminal directions suit in-cabinet routing
Ring-main units / cable junction boxes inlet24/250, 36/250Cable-through, bore d1 = 8/14 mm
36kV switchgear circuit bushings36/400, 36/630M16 stud, H = 332
Outdoor pole-mounted equipment / pad-mounted transformersBFGW-35KV/315AMulti-shed outdoor design, creepage 1256~1650 mm, four construction combinations

Why Xingda

Epoxy resin bushings are fully manufactured by Tianjin Xingda. Tooling for all three series and 27 specifications is in place and supply is stable; listed dimensions refer to standard products, and non-standard heights, special hole patterns and other terminal angles can be customized to customer drawings. The dry-type epoxy line is produced in the same factory as the five porcelain lines (GB, ANSI, NBR, DIN, EN), covering both oil-immersed and dry-type transformers from a single purchase. Every bushing is delivered with sealing and mounting flanges, ready to assemble on the tank cover.