The oil conservator system of an oil-immersed transformer relies on three basic protection accessories: a pressure relief valve — when an internal fault causes a sudden oil-pressure rise, the valve opens automatically at the set pressure to relieve it and re-seals after the fault is cleared, protecting the tank; an oil level gauge — a glass-tube-and-float construction directly showing the conservator oil level, with red Min./Max. marks; and an oil drain valve — fitted at the tank bottom or conservator lower end for oil sampling and draining during maintenance. For export markets Tianjin Xingda supplies all three accessories in 4 models (drawing numbers XD.YLSFF.10.S / XD.YLSFF.20.S / XD.YWJ.10.S / XD.FYF.20.S), with G1" and G1-1/2" connections.
Customisation: the operating pressure of the relief valves and the tank-opening dimensions of every unit can be customised to customer requirements (as stated in the original catalogue); gauge head height H and total length L of the oil level gauge are matched to the conservator; float Φ22±0.5.
Drawing-number naming: XD.YLSFF (pressure relief valve) / XD.YWJ (oil level gauge) / XD.FYF (oil drain valve) – size code .S (export type, for export only).
Table 1 | Pressure relief valves (2 models)
| Drawing No. | Connection | Cap outer dia. | Wrench size SW | Total height | Cap height | Thread section | Signal terminal | Cap label | Tank opening |
|---|---|---|---|---|---|---|---|---|---|
| XD.YLSFF.10.S | G1" | Φ55 | SW45 | ~72 | 25 / 32 | ~40 | M5 | LABEL: DO NOT OPEN | Φ41 |
| XD.YLSFF.20.S | G1-1/2" | Φ72 | SW50 | ~72 | ~32 | ~40 (15) | M5 | — | Φ53.5 |
※ Cap-height column: model 10 has two segments (flange 25 / inner 32); model 20 is ~32. Operating pressure on request; spring + seal construction opens automatically on overpressure and resets after relief.
Table 2 | Oil level gauge (1 model)
| Drawing No. | Connection | Wrench size SW | Head height | Thread length | Float outer dia. | Float height | Indication | Tank opening |
|---|---|---|---|---|---|---|---|---|
| XD.YWJ.10.S | G1" | SW45 | 82±2 | 16 | Φ22±0.5 | 46±1 | Glass tube + float, direct reading, red Min./Max. marks | Φ41 |
※ Total height H and total length L are variable, matched to the conservator height (head ~H, lower connection ~L, 6 = reserve at the end); the float rises and falls with the oil level, read directly on the tube scale.
Table 3 | Oil drain valve (1 model)
| Drawing No. | Total height | Top outer dia. | Base outer dia. | Oil outlet | Seal-pin hole | Groove sections | Tank opening |
|---|---|---|---|---|---|---|---|
| XD.FYF.20.S | ~76 | Φ41 | Φ46 | Φ30 | Φ3 | 4 + 4 (two) | Φ31 |
※ Brass body with top-cover sealing, Φ30 outlet on the tank side; used for oil sampling and draining during maintenance.
| Application | Recommended set | Notes |
|---|---|---|
| Standard 10–35 kV distribution transformers | YLSFF.10.S + YWJ.10.S + FYF.20.S | Uniform G1" connections, openings Φ41/Φ31 — the most common combination |
| Larger power transformers, high oil volume | YLSFF.20.S (G1-1/2") | Φ72 large cap, Φ53.5 opening, larger relief flow area |
| Fully-sealed corrugated conservators / complete export units | Three-piece set + XS breather (open conservators) | All accessories from one factory, fitted with the transformer in a single order |
| Special pressure classes / non-standard openings | Customised on request | Operating pressure and opening size both customisable |
The pressure relief valve, oil level gauge and oil drain valve are XD self-manufactured transformer accessories (export series), with brass bodies and metal caps for reliable sealing: the relief valve is spring-type with automatic reset, the gauge reads directly on a glass tube with red alarm marks, and the drain valve has a double-groove quick-mount design. Operating pressure and tank-opening dimensions can be customised to customer drawings; together with XD bushings, breathers and off-circuit tap changers, all accessories for an export transformer are produced in the same factory and shipped in one consolidated package.
Contact: Tianjin Juyida Technology Co., Ltd
WhatsApp: +86 13662056855
Tel:
E-mail: solomon20210701@tjxddq.com
Add: Unit‑101, Workshop 3, Bozhong Automobile Industrial Park, No.5 Xianghui Road, Intersection of Xianghui Road and Gaoying Road, Beizhakou Town, Jinnan District, Tianjin, China